AUDIT ENERGI LISTRIK DAN BOILER PABRIK KELAPA SAWIT KAPASITAS 60 TON/JAM

Authors

  • Muhamad Mustangin
  • Saptyaji Harnowo

DOI:

https://doi.org/10.47199/jaf.v2i1.131

Keywords:

Audit energy, Palm oil Mill, Electrical audit, Boiler Audit

Abstract

Palm Oil Factory Energy consists of steam and electricity. To increase the performance, energy will to be
audited. Electrical measurements are carried out at the power house, panels at each station and some electric
motors. Measurement in the main panel uses a power quality analyzer that can measure power, power factor,
harmonics, unbalance and other electrical parameters. For measurement of mechanical equipment with steam
energy such as boilers and turbines using temperature measuring devices with infrared thermal imaging tools
FLIR brand. The quality of electric power with a total harmonic of 5.12% and individual harmonics of 2.78%.
Voltage and current unbalance are 0.09% and 0.15%. Voltage drop is equal to 3 volts. The use of electricity
utilities is 22.81 kW / ton FFB. The factory has cos phi of 0.84 but requires automatic power factor correction.
The efficiency of boilers is 64.19% with the biggest losses being dry flue gas of 20.19% and oyher boiler of
67.82% with the biggest losses being dry flue gas of 16.45%.

Downloads

Download data is not yet available.

Author Biography

Muhamad Mustangin

Politeknik LPP

References

Ahmed, I. and Mir Zayed Shames, MZ. amd Alam,M. 2013. An Overview of Harmonic Sources in Power System. IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) Volume: 7 Issue 3 hal 01-03.

Ani, FN and Nor, NM, 2010, Energy index for palm oil processing in oil palm mills. Int J Quality and Innovation. Vol: 1 No. 2.

Firdaus, A. dan MS Ma’arif. 2016. Creating The Standard For Specific Energy Consumption At Palm Oil Industry. SINERGI Vol: 20, No. 1, hal 9-13.

IEEE-SA Standards Board. 2017. IEEE 3002 Standards:Power Systems Analysis: Recommended Practice for Conducting Harmonic Studies and Analysis of Industrial and Commercial Power Systems. The Institute of Electrical and Electronics Engineers, Inc. New York

IEEE-SA Standards Board. 2017. IEEE 3001 Standards: Power Systems Design : IEEE Std 3001.2™-2017:Recommended Practice for Evaluating the Electrical Service Requirements of Industrial and Commercial Power Systems. The Institute of Electrical and Electronics Engineers, Inc. New York.

Sommart, K. and Suneerat P. 2011. Assessment and Improvement of Energy Utilization in Crude Palm Oil Mill. International Conference on Chemistry and Chemical Process IPCBEE vol:10 IACSIT Press. Singapore.